34 | | 24 isolated noise-free channels |
35 | | |
36 | | Isolation on single channel at 3000V DC (1 min) |
37 | | |
38 | | Sampling frequency: 7,2 KHz |
39 | | |
40 | | Bandwidth (-3 dB): DC (0 Hz) ÷ 3,5 KHz |
41 | | |
42 | | Flat band (±0,005 dB): DC (0 Hz) ÷ 3,25 KHz |
43 | | |
44 | | Stop band attenuation: >100 dB |
45 | | |
46 | | Nominal Current (In): 1Arms / 5Arms |
47 | | |
48 | | Full-scale: 30?In |
49 | | |
50 | | Range of measure: 0,01?In ÷ 30?In |
51 | | |
52 | | Full-scale setup by software command |
53 | | |
54 | | Point error: < 0,5% |
55 | | |
56 | | Overload permanent: 40A |
57 | | |
58 | | Overload transitory: 150A (for 1 s) |
59 | | |
60 | | Input impedance: 1,5 mohm (purely resistive) |
61 | | |
62 | | Absorbed power (1A): 1,5 mVA @ In |
63 | | |
64 | | Absorbed power (5A): 37,5 mVA @ In |
65 | | |
66 | | Resolution (ENOB): 16 bit noise-free |
67 | | |
68 | | signal-noise ratio: 92 dB |
69 | | |
70 | | Cross-over: < -92 dB |
| 28 | * 24 isolated noise-free channels |
| 29 | * Isolation on single channel at 3000V DC (1 min) |
| 30 | * Sampling frequency: 7,2 KHz |
| 31 | * Bandwidth (-3 dB): DC (0 Hz) ÷ 3,5 KHz |
| 32 | * Flat band (±0,005 dB): DC (0 Hz) ÷ 3,25 KHz |
| 33 | * Stop band attenuation: >100 dB |
| 34 | * Nominal Current (In): 1Arms / 5Arms |
| 35 | * Full-scale: 30?In |
| 36 | * Range of measure: 0,01?In ÷ 30?In |
| 37 | * Full-scale setup by software command |
| 38 | * Point error: < 0,5% |
| 39 | * Overload permanent: 40A |
| 40 | * Overload transitory: 150A (for 1 s) |
| 41 | * Input impedance: 1,5 mohm (purely resistive) |
| 42 | * Absorbed power (1A): 1,5 mVA @ In |
| 43 | * Absorbed power (5A): 37,5 mVA @ In |
| 44 | * Resolution (ENOB): 16 bit noise-free |
| 45 | * signal-noise ratio: 92 dB |
| 46 | * Cross-over: < -92 dB |
76 | | 8 isolated noise-free channels |
77 | | |
78 | | Isolation on single channel at 3000V DC (1 min) |
79 | | |
80 | | Sampling frequency: 7,2 KHz |
81 | | |
82 | | Bandwidth (-3 dB): DC (0 Hz) ÷ 3,5 KHz |
83 | | |
84 | | Flat band (±0,005 dB): DC (0 Hz) ÷ 3,25 KHz |
85 | | |
86 | | Stop band attenuation: >100 dB |
87 | | |
88 | | Full-scale (Pn): 100Vrms / 200Vrms / 700Vrms |
89 | | |
90 | | Field of measure: |
91 | | |
92 | | 14 mVrms ÷ 100 Vrms @ Pn=100 Vrms |
93 | | |
94 | | 28 mVrms ÷ 200 Vrms @ Pn=200 Vrms |
95 | | |
96 | | 0,1 Vrms ÷ 700 Vrms @ Pn=700 Vrms |
97 | | |
98 | | Full-scale setup by software command |
99 | | |
100 | | Point error: < 0,5% |
101 | | |
102 | | Input impedance: 330 kohm (purely resistive) |
103 | | |
104 | | Absorbed power: 480 mVA @ 400V |
105 | | |
106 | | Resolution (ENOB): 16 bit noise-free |
107 | | |
108 | | signal-noise ratio: 92 dB |
109 | | |
110 | | Cross-over: <-86 dB |
| 52 | * 8 isolated noise-free channels |
| 53 | * Isolation on single channel at 3000V DC (1 min) |
| 54 | * Sampling frequency: 7,2 KHz |
| 55 | * Bandwidth (-3 dB): DC (0 Hz) ÷ 3,5 KHz |
| 56 | * Flat band (±0,005 dB): DC (0 Hz) ÷ 3,25 KHz |
| 57 | * Stop band attenuation: >100 dB |
| 58 | * Full-scale (Pn): 100Vrms / 200Vrms / 700Vrms |
| 59 | * Field of measure: |
| 60 | 14 mVrms ÷ 100 Vrms @ Pn=100 Vrms |
| 61 | 28 mVrms ÷ 200 Vrms @ Pn=200 Vrms |
| 62 | 0,1 Vrms ÷ 700 Vrms @ Pn=700 Vrms |
| 63 | * Full-scale setup by software command |
| 64 | * Point error: < 0,5% |
| 65 | * Input impedance: 330 kohm (purely resistive) |
| 66 | * Absorbed power: 480 mVA @ 400V |
| 67 | * Resolution (ENOB): 16 bit noise-free |
| 68 | * signal-noise ratio: 92 dB |
| 69 | * Cross-over: <-86 dB |