Version 12 (modified by Logiclabsrl, on 01/26/07 at 16:59:07) (diff) |
---|
Fault Recorder
LogicLab? RTEMS-based fault recorder characteristics
Tecnical informations
Power supply
- Power Supply (Vaux): 110V DC ± 20% (more options available)
- Power request: 40W
- Voltage dips and short interruptions Insensitive to 100% of Vaux for 50 ms (min) Insensitive to 50% of Vaux for 100ms (min)
Dimensions
- Height: 9HE
- Width: 19"
- Depth: 31 cm
Current inputs
- 24 isolated noise-free channels
- Isolation on single channel at 3000V DC (1 min)
- Sampling frequency: 7,2 KHz
- Bandwidth (-3 dB): DC (0 Hz) ÷ 3,5 KHz
- Flat band (±0,005 dB): DC (0 Hz) ÷ 3,25 KHz
- Stop band attenuation: >100 dB
- Nominal Current (In): 1Arms / 5Arms
- Full-scale: 30?In
- Range of measure: 0,01?In ÷ 30?In
- Full-scale setup by software command
- Point error: < 0,5%
- Overload permanent: 40A
- Overload transitory: 150A (for 1 s)
- Input impedance: 1,5 mohm (purely resistive)
- Absorbed power (1A): 1,5 mVA @ In
- Absorbed power (5A): 37,5 mVA @ In
- Resolution (ENOB): 16 bit noise-free
- signal-noise ratio: 92 dB
- Cross-over: < -92 dB
Voltage inputs
- 8 isolated noise-free channels
- Isolation on single channel at 3000V DC (1 min)
- Sampling frequency: 7,2 KHz
- Bandwidth (-3 dB): DC (0 Hz) ÷ 3,5 KHz
- Flat band (±0,005 dB): DC (0 Hz) ÷ 3,25 KHz
- Stop band attenuation: >100 dB
- Full-scale (Pn): 100Vrms / 200Vrms / 700Vrms
- Field of measure: 14 mVrms ÷ 100 Vrms @ Pn=100 Vrms 28 mVrms ÷ 200 Vrms @ Pn=200 Vrms 0,1 Vrms ÷ 700 Vrms @ Pn=700 Vrms
- Full-scale setup by software command
- Point error: < 0,5%
- Input impedance: 330 kohm (purely resistive)
- Absorbed power: 480 mVA @ 400V
- Resolution (ENOB): 16 bit noise-free
- signal-noise ratio: 92 dB
- Cross-over: <-86 dB
Digital inputs
- 128 isolated channels
- Isolation on single channel at 3000V DC (1 min)
- Input voltage (min): 18V
- Input voltage (max): 140V
- Time resolution: 1 ms
Communication
Ethernet 10/100 Mbit/s
Configurable as knot of a net LAN/WAN
1 RS232 (19.200 fixed bauds) – frontal side
1 RS232 (until 115.200 bauds) – back side
Remote connection with analog modem
3 RS232 for custom applications
Isolated communication ports
(Ethernet: 1500 Vrms Serials: 2500 Vrms)
Connector for satellite antenna
Signal relay
Out of order
Recording in progress
Elaboration
32 bit multiprocessor (4 ColdFire? MCF5272processor) system
Realtime operating system RTEMS
32 MByte Flash memory
128 Mbyte DRAM
RTC with GPS synchronization
Fault Recording Recording in flash memory
Recording maximum time: 250 s
Maximum number of recordings: 180
Pre-fault time: 50 ms ÷ 1 s
Fault time: 100 ms ÷ 60 ses
Post-fault time: 100 ms ÷ 1 s
Possibility of prolongation recording
Maximum duration recording: 150 s
Analog Trigger on threshold (max, min, gradient)
Trigger on digital transitions
GPS based time tag events (Precision: 1 µs - Resolution: 1 ms)
Normative conformity
IEC 61000 – 4 – 2 (Level 3)
IEC 61000 – 4 – 3 (Level 3)
IEC 61000 – 4 – 4 (Level 3)
IEC 61000 – 4 – 5 (Level 4)
IEC 61000 – 4 – 6 (Level 3)
IEC 61000 – 4 – 8 (Level 5)
IEC 61000 – 4 – 10 (Level 3)
IEC 61000 – 4 – 12 (Level 3)
IEC 61000 – 4 – 16 (Level 4)
IEC 61000 – 4 – 17 (Level 3)
IEC 61000 – 4 – 29 (Level 3)
ENEL DV1047A2-NC
ENEL REMC01
ENEL REMC02
ENEL RMEC01
ENEL RCLI01
ENEL LV27
ENEL LV29
ENEL DV1500
ENEL DV1501 A
ENEL DN7600
CEI 45-5
CEI 70-1 IP30 (front) IP20 (case)
COMTRADE standard IEEE Std C37.111-1991
Firmware Architecture
In progress...
Link
Product brochure:
[English: http://www.logiclab.it/DV947_file/Fault%20recorder%20LogicLab.pdf]
[Italian: http://www.logiclab.it/DV947_file/BrochureOscilloperturbografo.pdf]
Italian site:
[LogicLab: http://www.logiclab.it]
[PowerProbe: http://www.logiclab.it/it/DV947.htm]
RTEMS related page: