    3 =  '''Power supply'''  =
    43
     4=  Techinical information  =
     5
     6
     7'''Power supply'''
    58
    69Power Supply (Vaux):  110V DC ± 20% (more options available)
     
    1316
    1417        Insensitive to 50% of Vaux for 100ms (min)
    15 =  '''Dimensions'''  =
    1618
     19----
     20
     21'''Dimensions'''
    1722
    1823Height:  9HE
     24
    1925Width:  19"
     26
    2027Depth:  31 cm
    21 =  '''Current inputs'''  =
    2228
     29----
    2330
    24 24 isolated noise-free channels
     31'''Current inputs'''
     32
     3324 isolated noise-free channels
     34 
    2535Isolation on single channel at 3000V DC (1 min)
     36
    2637Sampling frequency:  7,2 KHz
     38
    2739Bandwidth (-3 dB): DC (0 Hz) ÷ 3,5 KHz
     40
    2841Flat band (±0,005 dB): DC (0 Hz) ÷ 3,25 KHz
     42
    2943Stop band attenuation:  >100 dB
     44
    3045Nominal Current (In): 1Arms / 5Arms
     46
    3147Full-scale:  30?In
     48
    3249Range of measure:  0,01?In ÷ 30?In
     50
    3351Full-scale setup by software command
     52
    3453Point error:  < 0,5%
     54
    3555Overload permanent:  40A
     56
    3657Overload transitory:  150A (for 1 s)
     58
    3759Input impedance:  1,5 mohm (purely resistive)   
     60
    3861Absorbed power (1A): 1,5 mVA @  In
     62
    3963Absorbed power (5A): 37,5 mVA @  In
     64
    4065Resolution (ENOB): 16 bit noise-free
     66
    4167signal-noise ratio:  92 dB
     68
    4269Cross-over:  <  -92 dB
    4370
    44 =  '''Voltage inputs'''  =
     71----
    4572
     73'''Voltage inputs'''
    4674 