| 1 | = Automatic Load Shed = |
| 2 | |
| 3 | |
| 4 | LogicLab RTEMS-base Automatic Load Shed |
| 5 | = Hardware technical data = |
| 6 | |
| 7 | = Power Supply = |
| 8 | |
| 9 | |
| 10 | Power supply voltage: 110V DC ± 20% |
| 11 | * Medium power: 20W |
| 12 | * Voltage dips and short interruptions |
| 13 | Insensitive to 100% of Vaux for 50 ms (min) |
| 14 | Insensitive to 50% of Vaux for 100ms (min) |
| 15 | = Dimensions = |
| 16 | |
| 17 | * Height: 3U |
| 18 | * Width: 19” |
| 19 | * Depth: 34cm |
| 20 | = Voltage inputs = |
| 21 | |
| 22 | * 4 isolated voltage input channels |
| 23 | * 6 inputs on 3 voltage channels with fullscale 100V (M2) |
| 24 | * 1 inputs on 1 voltage channel with fullscale 400V (M1) |
| 25 | * Dielectric strength 3000V DC (1 min) |
| 26 | * Rated Voltage (Vn) M1: |
| 27 | 57Vrms |
| 28 | 100Vrms |
| 29 | 400Vrms |
| 30 | * Rated Voltage (Vn) M2: |
| 31 | 57Vrms |
| 32 | 100Vrms |
| 33 | * Operating range: 0.01 ÷ 1.6 Vn |
| 34 | * Rated voltage selection (Vn): software |
| 35 | * Frequency Range: 10 ÷ 130 Hz |
| 36 | * Permanent overload capability: 1.5 Vn |
| 37 | * Transient overload capability - not measurable(<10s): 2Vn |
| 38 | * Power dissipation: |
| 39 | <1VA @Vn = 400V |
| 40 | <0,1VA @Vn = 100V |
| 41 | * Accuracy: |
| 42 | * RMS value: ±0,001 Vn |
| 43 | * Voltage rate: ±0,002 Vn/S |
| 44 | * Frequency: ±0,002 Hz @ Vn |
| 45 | * 0,01 Hz @ V>0,3VnVn |
| 46 | * 0,02 Hz @ V<0,3Vn |
| 47 | * Frequency rate: ±0,002 Hz/s |
| 48 | = Alarms (digital outputs)*** |
| 49 | * 15 Relays |
| 50 | * Out of order |
| 51 | * 81/81R Threshold 1 |
| 52 | * 81/81R Threshold 2 |
| 53 | * 81/81R Threshold 3 |
| 54 | * 81/81R Threshold 4 |
| 55 | * 27/59/27R Threshold 1 |
| 56 | * 27/59/27R Threshold 2 |
| 57 | * Stop threshold Min/Max voltage and/or voltage imbalance |
| 58 | * Stop threshold maximum frequency difference |
| 59 | * 27/59/27R/81/81R Threshold 1 |
| 60 | * 27/59/27R/81/81R Threshold 2 |
| 61 | * 81/81R Threshold 3 and/or 4 |
| 62 | * General alarm |
| 63 | * Relay available on connector C1 |
| 64 | * Relay available on connector C2 |
| 65 | * Dielectric strength 3300V DC (1 min) |
| 66 | * Rated voltage: 110V |
| 67 | * Rated current: 5A |
| 68 | * Maximum Switching Capacity (L/R=40ms): 0,5A @110V |
| 69 | * Endurance (mechanical): ?10e7 |
| 70 | |
| 71 | =Digital inputs=== |
| 72 | |
| 73 | * 2 isolated inputs |
| 74 | * Input signal close status HV switch (Red line) |
| 75 | * Input signal close status HV switch (Green line) |
| 76 | * Dielectric strength 33000V DC (1 min) |
| 77 | * Threshold voltage: 60V ± 10% |
| 78 | * Input Voltage (max): 140V |
| 79 | * Time resolution: 1 ms |
| 80 | = Current outputs = |
| 81 | |
| 82 | * 4 current loop transmitters |
| 83 | * Dielectric strength 33000V DC (1 min) |
| 84 | * Current range: 4-20mA or ±5mA software selectable |
| 85 | * Accuracy: <0,5% |
| 86 | * Transient: <200ms |
| 87 | * Maximum load: |
| 88 | * <2K? @ ±5mA |
| 89 | * <1K? @ 4÷20mA |
| 90 | = Communication = |
| 91 | |
| 92 | * HMI with 4 lines display and keypad |
| 93 | * 16 LED |
| 94 | * Local and remote interface |
| 95 | * Ethernet 10/100 BASE-TX with auto MDI/MDI-X |
| 96 | * Ethernet 100BASE-FX (SC) - optical link |
| 97 | * Configurable as knot of a net LAN/WAN |
| 98 | * 1 RS232 front side (19.200 baud fixed) |
| 99 | * 1 RS232 back side (up to 115.200 baud) |
| 100 | * Remote connection with analog modem (not included) |
| 101 | * Isolated comunication port |
| 102 | (Ethernet: 1500Vrms – Serials: 2500 Vrms) |
| 103 | * Field connection with 50 pins rectangular connectors |
| 104 | = Customizing = |
| 105 | |
| 106 | * Power Supply with different input voltage |
| 107 | * Different full-scales on voltage inputs on client demand |
| 108 | * Up to 6 digital inputs available for custom application |
| 109 | * 24V digital input with threshold 18V ± 10% |
| 110 | * Custom range for current outputs |
| 111 | * HMI multi functions |
| 112 | * Additional Ethernet port 10/100BASE-TX backside |
| 113 | * ST connector for ethernet 100BASE-FX optical link |
| 114 | * Configuration parameters and thresholds are modifiable at the request within the limits of the device |
| 115 | * Integrated WebServer for parameterization with Internet Browser |
| 116 | * FTPserver for record download |
| 117 | * Different range for recording time |
| 118 | * AC digital input |
| 119 | * Optional relay outputs |
| 120 | * Different logical assignments to alarm |
| 121 | = Standards and specifications compliance = |
| 122 | |
| 123 | * IEC 61000 – 4 – 2 (Level 3) |
| 124 | * IEC 61000 – 4 – 3 (Level 3) |
| 125 | * IEC 61000 – 4 – 4 (Level 3) |
| 126 | * IEC 61000 – 4 – 5 (Level 4) |
| 127 | * IEC 61000 – 4 – 6 (Level 3) |
| 128 | * IEC 61000 – 4 – 8 (Level 5) |
| 129 | * IEC 61000 – 4 – 10 (Level 3) |
| 130 | * IEC 61000 – 4 – 12 (Level 3) |
| 131 | * IEC 61000 – 4 – 16 (Level 4) |
| 132 | * IEC 61000 – 4 – 17 (Level 3) |
| 133 | * IEC 61000 – 4 – 29 (Level 3) |
| 134 | * ENEL DV938 |
| 135 | * ENEL REMC01 |
| 136 | * ENEL REMC02 |
| 137 | * ENEL RMEC01 |
| 138 | * ENEL RCLI01 |
| 139 | * CEI 45-5 |
| 140 | * CEI 70-1 IP30 (front) IP20 (case) |
| 141 | * COMTRADE standard IEEE Std C37.111-1991 |